Electrical · CEC Rule 8-102

Voltage Drop Calculation in Canada — CEC Rule 8-102 Explained

The 3% and 5% mandatory limits, the formula, and when to upsize wire for long runs.

Calculate voltage drop now: Voltage Drop Calculator (CEC Rule 8-102) →

What is voltage drop and why the CEC limits it

Voltage drop is the reduction in voltage that occurs as current flows through the resistance of a wire. Every conductor has resistance, and the longer and thinner the wire, the greater the resistance — and the greater the voltage drop along its length.

Excessive voltage drop causes real problems: motors run hotter and wear out faster, LED drivers flicker or fail, and sensitive electronics may malfunction. A circuit that loses too much voltage at the load end is effectively delivering less power than it was designed to provide.

The Canadian Electrical Code addresses this in Rule 8-102, which sets mandatory limits on how much voltage a circuit is permitted to drop. Unlike the US National Electrical Code, which only recommends limits in a non-enforceable fine-print note, CEC Rule 8-102 is mandatory — installations that exceed the limits do not pass inspection.

CEC Rule 8-102: the 3% and 5% limits

Rule 8-102 sets two voltage drop limits that both must be met:

In practice, for a residential circuit on a modern 200A panel close to the meter, the feeder drop is negligible and the 3% branch circuit limit is the binding constraint.

The voltage drop formula

The standard formula for single-phase AC circuits (also used for DC):

VD (volts) = (2 × L × I × R) / 1000

To convert to a percentage:

VD% = (VD ÷ system voltage) × 100

Worked example: 20A circuit, 25-metre run, 120V system, 12 AWG wire (R = 5.31 mΩ/m).
VD = (2 × 25 × 20 × 5.31) / 1000 = 5,310 / 1000 = 5.31V
VD% = (5.31 / 120) × 100 = 4.4% — exceeds the 3% CEC limit.
Solution: upsize to 10 AWG (R = 3.33 mΩ/m): VD = (2 × 25 × 20 × 3.33) / 1000 = 3.33V = 2.8%

Voltage drop by wire gauge — 120V circuit, 30-metre run

The table below shows the voltage drop and percentage for a 30-metre one-way run at two common circuit sizes. Values exceeding the 3% CEC limit are marked.

Wire sizeResistance (mΩ/m)15A circuit (12A load)20A circuit (16A load)
14 AWG8.464.1V / 3.4%5.4V / 4.5%
12 AWG5.312.5V / 2.1%3.4V / 2.8%
10 AWG3.331.6V / 1.3%2.1V / 1.8%
8 AWG2.11.0V / 0.8%1.3V / 1.1%
6 AWG1.320.6V / 0.5%0.8V / 0.7%

Load = 80% of breaker rating per CEC Rule 8-104. Resistance from CEC Table 2 (copper). Red = exceeds 3% CEC Rule 8-102 limit.

CEC vs NEC: why US tools give wrong answers in Canada

The most common error Canadian electricians encounter when using US-built voltage drop calculators is that the US tools treat the 3% limit as a recommendation, not a hard requirement. A US calculator may show a result of 3.5% and not flag it as non-compliant — because in the US, it technically isn't.

In Canada, any branch circuit exceeding 3% under CEC Rule 8-102 is non-compliant and must be corrected before the installation will pass inspection. The standard is mandatory, not advisory.

US tools also commonly use NEC wire ampacity tables, which differ from CEC Table 2 in their temperature correction factors and some conductor ratings. Always use a CEC-based calculator for work done in Canada.

Check your circuit now: Voltage Drop Calculator — CEC Rule 8-102 compliant →

Frequently asked questions

What is the maximum voltage drop allowed by the Canadian Electrical Code?
CEC Rule 8-102 sets two limits: a branch circuit must not exceed 3% voltage drop, and the combined feeder plus branch circuit must not exceed 5% total. On a 120V circuit, 3% equals 3.6V maximum drop. On a 240V circuit, 3% equals 7.2V. These limits are mandatory in Canada — they are not recommendations like the equivalent NEC guidance in the United States.
How is Canadian voltage drop different from the US NEC?
The Canadian Electrical Code (CEC Rule 8-102) makes voltage drop limits mandatory — an installation that exceeds 3% on a branch circuit does not meet code and will not pass inspection. The US National Electrical Code (NEC) only recommends a 3% limit in a fine-print note; it is not enforceable. This means US voltage drop calculators and charts designed for NEC do not reflect the same compliance standard. Canadian electricians must meet the CEC limit to pass inspection.
What wire size should I use for a long run to reduce voltage drop?
For runs over 20–25 metres on a 15A or 20A circuit, voltage drop often requires upsizing beyond the minimum ampacity wire. A 20A circuit on a 30-metre run at 120V requires 10 AWG instead of the minimum 12 AWG to stay within 3%. Use the Voltage Drop Calculator to find the correct size for your specific run length, amperage, and voltage.

Code reference

Need a licensed electrician?

Get connected with a CEC-certified electrician in your area for panel work, long-run circuits, and permit applications.

✓ Free    ✓ No obligation    ✓ Licensed contractors only