Standard and code basis

Voltage drop limits in Canada are set by CEC Rule 8-102 (CSA C22.1-21):

  • Branch circuits: Maximum 3% voltage drop from the panel to the load.
  • Feeders: Maximum 2% voltage drop from the service entrance to the sub-panel.
  • Total (service to load): The CEC recommends a combined maximum of 5% — meaning if a feeder drops 2%, the branch circuit should drop no more than 3%.

The resistivity values used — 0.0172 Ω·mm²/m for copper and 0.0282 Ω·mm²/m for aluminum — are the standard conductivity values recognized by the CEC for ambient temperature conductor resistance.

Your inputs — what each field means

InputWhat it representsEffect on result
Load current (amps)The current the circuit carries under full loadVoltage drop is directly proportional to current. Doubling the current doubles the drop.
Wire size (AWG)The conductor gauge being evaluatedLarger conductors (lower AWG number) have more cross-section (mm²), reducing resistance and voltage drop.
Conductor materialCopper or aluminumCopper resistivity: 0.0172 Ω·mm²/m. Aluminum: 0.0282 Ω·mm²/m. Aluminum drops 64% more than copper for the same gauge.
One-way run length (m)The distance from panel to load in metresVoltage drop is proportional to run length — and the formula uses 2× the one-way length to account for both the supply and return conductors.
System voltageThe nominal voltage of the circuitDrop percentage = (Vd ÷ system voltage) × 100. A 2V drop on a 240V circuit is 0.8%; on a 120V circuit it is 1.7%.
Circuit typeBranch circuit or feederDetermines the applicable CEC limit: 3% for branch circuits, 2% for feeders.

The calculation — step by step

  1. Look up conductor cross-section (mm²). The AWG gauge you enter is matched to its metric cross-section from CEC Table 2. For example: 12 AWG copper = 3.31 mm²; 10 AWG = 5.26 mm²; 8 AWG = 8.37 mm²; 6 AWG = 13.3 mm².
  2. Apply the voltage drop formula:
    Vd = (ρ × 2 × L × I) / A
    Where:
    • ρ = resistivity in Ω·mm²/m (0.0172 copper, 0.0282 aluminum)
    • L = one-way run length in metres
    • I = current in amps
    • A = conductor cross-section in mm²
    • The factor of 2 accounts for both the supply conductor and the return (neutral or ground) conductor
  3. Calculate drop percentage:
    VD% = (Vd ÷ system voltage) × 100
  4. Compare against CEC limit. Branch circuit: pass if VD% ≤ 3%. Feeder: pass if VD% ≤ 2%.
  5. Calculate voltage at load:
    voltage at load = system voltage − Vd
    This is the actual voltage available at the receptacle or appliance terminals.

Reading your result

  • Voltage drop (V): The absolute voltage lost across the conductor run.
  • Voltage drop (%): Drop as a percentage of system voltage. This is the number compared against the CEC 3% or 2% limit.
  • CEC compliant: Whether the drop is within the applicable limit for your circuit type.
  • Voltage at load: The voltage available at the end of the run — useful for checking whether sensitive equipment (motors, dimmers) will receive adequate voltage.

If the result shows non-compliant, increase the wire gauge (lower AWG number) and re-run the calculation. The wire size calculator can also determine the minimum gauge required to keep both ampacity and VD within limits simultaneously.

Assumptions and limitations

  • Uses DC resistivity formula. AC circuits have a slightly lower actual drop due to power factor — this calculator produces a conservative (higher) result, which is standard engineering practice.
  • Assumes ambient temperature of 30°C. Higher ambient temperatures increase conductor resistance; the error is small (<2%) for typical Canadian installation temperatures.
  • Does not account for conduit material effects (steel vs. PVC) on AC impedance — the difference is minor for most residential and commercial applications.
  • For 3-phase circuits, the formula changes — the factor of 2 becomes √3 (approximately 1.732). This calculator is for single-phase circuits only.

Ready to calculate?

Check voltage drop for any Canadian branch circuit or feeder.

Use the Voltage Drop Calculator