Standard and code basis

Overcurrent protection sizing in Canada is governed by CEC Rule 14-104 (CSA C22.1-21), which states:

  • The rating of an overcurrent device must not be less than the ampacity of the conductors it protects.
  • For continuous loads (loads expected to run for 3 hours or more), the overcurrent device must be rated at no less than 125% of the continuous load current. This prevents the breaker from running at its thermal limit continuously, which accelerates breaker aging and can cause nuisance tripping.
  • The selected breaker size must be a standard rating from the CEC-recognised series: 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200A.

Your inputs β€” what each field means

InputWhat it representsHow it affects the result
Load (watts)The nameplate wattage of the appliance or circuitDivided by voltage to get amps. Larger loads require larger breakers.
Voltage (120V or 240V)Whether this is a single-pole (120V) or double-pole (240V) circuitamps = watts Γ· voltage. A 2,400W load at 240V draws 10A; the same load at 120V draws 20A.
Continuous loadWhether the load runs for 3+ hours uninterruptedIf yes, the calculated amps are multiplied by 1.25 before selecting the breaker size. HVAC compressors, EV chargers, and lighting circuits are typically continuous.

The calculation β€” step by step

  1. Convert watts to amps:
    amps = watts Γ· voltage
    Example: 3,600W range hood at 240V = 15A.
  2. Apply the continuous load factor (if applicable):
    required amps = amps Γ— 1.25 (continuous) or amps Γ— 1.0 (non-continuous)
    Example: 15A continuous load β†’ 15 Γ— 1.25 = 18.75A required.
  3. Select the next standard breaker size:
    The calculator scans the standard CEC breaker size series and selects the first size at or above the required amps:
    15 β†’ 20 β†’ 25 β†’ 30 β†’ 35 β†’ 40 β†’ 45 β†’ 50 β†’ 60 β†’ 70 β†’ 80 β†’ 90 β†’ 100A (and above)
    Example: 18.75A required β†’ 20A breaker selected.
  4. Determine minimum wire size:
    The calculator also returns the minimum conductor size for the selected breaker, based on the CEC ampacity pairing table (e.g., 15A β†’ 14 AWG; 20A β†’ 12 AWG; 30A β†’ 10 AWG).
  5. Determine poles:
    120V circuits use a 1-pole breaker. 240V circuits use a 2-pole breaker.

Reading your result

  • Calculated amps: The raw watts Γ· voltage result, before the continuous factor is applied.
  • Required amps: The amps after applying the 1.25 factor (if continuous). This is the threshold the breaker must exceed.
  • Breaker size: The minimum standard CEC breaker size that meets or exceeds the required amps.
  • Poles: 1-pole for 120V, 2-pole for 240V.
  • Minimum wire (AWG): The smallest wire gauge whose 75Β°C ampacity supports the selected breaker.

Assumptions and limitations

  • The continuous load definition (3-hour threshold) is from CEC Rule 14-104. If you are unsure whether your load qualifies, select β€œcontinuous” β€” it produces a conservative (larger) result.
  • This calculator does not account for motor loads, which have additional starting current requirements under CEC Rules 28-200 and 28-204. Motor-driven equipment requires a separate motor protection calculation.
  • GFCI and AFCI requirements (CEC Rules 26-700 and 26-724) depend on circuit location and jurisdiction β€” this calculator does not determine GFCI/AFCI requirements, only the breaker ampere rating.
  • Power factor is not accounted for. For resistive loads (heaters, incandescent lighting) this has no effect. For inductive loads (motors, transformers) with a power factor below 0.85, consult a licensed electrician.

Ready to calculate?

Enter your load wattage and get an instant CEC Rule 14-104 breaker size.

Use the Circuit Breaker Calculator